APC DP300E Series Power Supply User Manual


 
20 User Guide Silcon DP300E Series 480V 400-500kVA
7OA0004 US rev. 02
4.4 Programming of battery monitor
Action Display shows
1. Press
and simultaneously to open
for password input
2. Enter password xx xx xx by pressing
3. Press
or until
4. Enter the expected back-up time in min. at
100% ohmic (pf = 1) load, when the inverter
has a mean efficiency of approx. 96%
Press
I.e. 14.0 min.
5. Press
to store data
6. Press or until
7 Press to set Ah for battery
8. Press to store data
9. Press
to exit
Installation of new batteries:
When installing new batteries the procedure in section 4.4 MUST be carried out,
otherwise the monitor may give false alarms.
Programming Parameters
Key in password
:
Last selected
parameter
Expected back-up
time [min.]: XXX.X
Expected back-up
time [min.]: 14.0
Data stored
Battery capacity
in [Ah]: XX.X
Battery capacity
in [Ah]: 7.0
Data stored
Normal operation
load power XX%
NOTE:
Only for APC personnel and
certified local APC personnel.