APC 5000 Power Supply User Manual


 
34001813EN/AE - Page 35
2. Installation
Characteristics of the contacts on the relay communications card.
Communications card connection example
If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from the
upstream source to ensure the safety of personnel working on the installation.
Adding communication cards
Characteristics of the output contacts:
Permissible voltage: 250V AC, 30V DC.
Permissible current: 2 A.
Cable : 4 x 0.93 mm
2
, Ø 6.6 ± 0.3 mm.
Characteristics of the input contacts:
Switched voltage: 5 V DC
Consumption: 10 mA.
Cable: 4 x 0.34 mm
2
, Ø 5 ± 0.5 mm.
UPS OFF
UPS ON
6
5
4
3
2
1
BA
Low battery warning
Load on battery power
Load on automatic bypass
Load on UPS
Battery fault
General alarm
carte de
communication
source
Disconnecting device that can be locked
AC
communication
card
2
4
1
3