APC 7000 Power Supply User Manual


 
Specification guide
Single UPS, three-phase, 160 to 500 kVA
(cont.)
APC by Schneider Electric Edition - 01/2010 Single UPS spec - p.
10
- Ethernet 10/100 Mbps using one of the protocols below:
XML-Web for direct UPS connection to an intranet network, without connection to a server, capable of supplying
information via a standard web browser
SNMP for connection to a computer-network management system
ω multi-standard communications card with three outputs:
- the two outputs listed above
- plus a modem output for communication with a tele-maintenance system.
ω The UPS shall be detectable by supervision software for large UPS systems.
ω Shutdown and administration software shall be available in addition to the communication cards.
11. Maintainability
A manual bypass shall be available to completely isolate the UPS for maintenance purposes.
11.1. Local and remote diagnostics and monitoring - E. Services
The UPS shall be equipped with a self-test system to check operation of the system as a whole each time it is
started. To that end, the supply control/monitoring electronics shall offer:
ω
Auto-compensation of component drift
ω Acquisition of information vital for computer-aided diagnostics or monitoring (local or remote);
ω Overall readiness for remote supervision services provided by the manufacturer.
12. Standards and tests
12.1. Standards
All equipment shall be designed and built in accordance with accepted engineering practice and applicable
international standards, in particular the standards listed below.
ω IEC 60140-4: UPS - Performance.
ω IEC 62040-1 and EN 62040-1: UPS - Safety.
ω IEC 62040-2 and EN 62040-2: UPS - Electromagnetic compatibility (EMC), level B.
ω IEC 62040-3 and EN 62040-3: UPS - Performance.
ω IEC 60950 / EN 60950: Safety of IT equipment, including electrical business equipment.
ω IEC 61000-2-2: EMC, levels of compatibility.
ω IEC 61000-3-4: Limitation of emission of harmonic currents in low-voltage power supply systems for equipment
with rated current greater than 16 A.
ω IEC 61000-4: EMC, immunity tests.
ω IEC 439: Low-voltage switchgear and control gear assemblies.
ω IEC 60529: Degrees of protection provided by enclosures (IP Code).
ω ISO 3746: Sound power levels.
ω CE marking.
What is more, the equipment shall comply with eco-design and eco-manufacturing criteria in view of sustainable
development and to that end, the manufacturer shall be able to demonstrate:
ω R&D and production on an ISO 14001 certified site
ω Manufacture with over 90% recyclable materials
ω Capacity to recover products at the end of their service life and provide proof of destruction by a certified
organisation
ω The environmental profile of the product, which shall be supplied with the sales offer.
12.2. Certification of conformity
The manufacturer shall provide, on request, a complete qualification file demonstrating compliance with the above
standards. What is more, the indicated levels of performance shall be confirmed by certification from independent
laboratories (e.g. TÜV or VERITAS).
13. Quality system and test procedures
13.1. Test procedures
The manufacturer shall provide proof of a quality-assurance system. In particular, the main manufacturing steps
must be subject to suitable tests such as: