APC 990-1378 Power Supply User Manual


 
20 Installation Guide APC BC300 Series 10kW 208/450/480V UPS
990-1378
Installation
Notes:
1. 3- or 4-wire provided source.
2. Cables not provided by APC.
3. Recommended input over current protection (MIB) based on an 80% rated device.
4. All AC cables must be AC 3- or 4-wire 3-phase.
5. Keep UPS input, output and control cables in separate conduits.
6. Installation must comply with all applicable national and local codes.
UPS Model Input
Current
Output
Current
Recom-
mended
MIB
DC Voltage DC Current
10kW 208V 37A 28A 50AT 216V 50A
10kW 450V 17A 13A 25AT 216V 50A
10kW 480V 16A 12A 25AT 216V 50A
NOTICE!
You must provide overcurrent protection and UPS input AC disconnect means.
See the “Technical Specifications” section in this Installation Guide for recommended UPS input
and output overcurrent protection.
CAUTION!
UPS systems can be connected as 3-phase, a 3-wire plus ground, provided that the load is not
connected to the neutral conductor.
NOTICE!
Only authorized electricians may install the UPS and all applicable codes must be observed.
NOTICE!
Always keep AC, DC and communication cables separated.
NOTICE!
The grounding electrode conductor (Protective Earth - PE) must be the same size (ampacity) as
the UPS input circuit conductors. Conduit is not an acceptable grounding electrode conductor -
see National Electrical Code Section 250-91(a).
NOTICE!
The unit is wired from the factory as a separately derived system. Output neutral is bonded to
equipment ground through main bonding jumper inside the UPS. See National Electrical Code
Article 250-5(d) and 250-26 for correct installation grounding.
NOTICE!
The maintenance bypass switch must be a 4-pole device switching all three phases and neutral.
If you are using a 3-pole device, contact APC Technical Support for instructions on how to
convert the unit to a not-separately derived system.