8 Installation Guide APC BC300 Series 10kW 208/450/480V UPS
990-1378
Installation
3.2.1 Conduit Connection Kit Contents
For Pedestals:
23 pedestals
4 M8 x 100 mm bolts
4 M8 lock washers
4 M8 flat washers
4 M8 nuts
For Conduit Box:
1 Conduit Box
1 Conduit Box Cover
11 M5 x 12 mm T20 Torx screws
11 M5 lock washers
11 M5 flat washers
For Base Covers:
2 Side Base Covers
2 Front/Rear Base Covers
Hook and loop fasteners
3.2.2 Installing Pedestals
1) Remove brackets mounted to the UPS feet during shipping
2) Lift the UPS off the floor and place the pedestals under UPS feet where the holes of
pedestals and holes in UPS feet are aligned
3) With caution lower the UPS feet into pedestal
4) Fasten but DO NOT TIGHTEN bolts, washers and nuts on the four corner feet of UPS
5) Move the UPS to the installation site
Tighten the bolts
3.2.3 Installing Conduit Box and Base Covers
1) Punch conduit holes in the back of the conduit box
2) Place the conduit box between the center leg and right leg of the unit, with the open side
facing the front of the unit
CAUTION!
Heavy Equipment. Use caution and appropriate equipment to safely lift the UPS several inches
above the floor when installing pedestals.
NOTICE!
Place flat washer under the bolt head and the lock washer under the nut.