APC AP9212 Switch User Manual


 
MasterSwitch Power Distribution Unit User’s Guide 11
Menu Items
Outlets
Outlet Control
Actions
You can perform the following Outlet Control Actions on individual
outlets or on all accessible outlets as a group (by
Master Outlet Control).
You can apply a Control Action only to an outlet that is not executing a
command.
Item Definition
Immediate On
The outlet turns on.
Immediate Off
The outlet turns off.
Immediate Reboot
The outlet turns off immediately, waits the outlet’s Reboot
Duration time, and turns on.
Delayed On
The outlet turns on according to its Power On Delay.
Delayed Off
The outlet turns off according to its Power Off Delay.
Sequenced Reboot
All outlets in the group assigned to the outlet user
immediately turn off. Each outlet then waits the longest
Reboot Duration (in seconds) of any outlet in the group,
waits its own Power On Delay, and turns on.
Delayed Reboot
The outlet turns off after its Power Off Delay, waits its own
Reboot Duration, and turns on.
Delayed Sequenced
Reboot
Each outlet in the group of accessible outlets does the
following:
1. Waits its own Power Off Delay.
2. Turns off.
3. Waits the longest Reboot Duration time (in seconds) of
any outlet in the group.
4. Waits its own Power On Delay.
5. Turns on.
Cancel Pending
Commands
All pending commands are canceled for the outlet(s).
Note: The Outlet State appears in orange with an asterisk
(*), indicating that a command is pending for the
outlet(s).