APC AP9618 Network Card User Manual


 
6 Installation and Quick-Start Manual
Installation in a UPS
Overview You can install the Management Card in a card slot in a
Smart-UPS, Matrix-UPS, or Symmetra. For a Silcon UPS, the
Management Card installs in a Silcon Triple Expansion
Chassis (AP9604S).
Step 1: Turn off
all power
(Smart-UPS or
Matrix-UPS)
You do not need to turn power off for a Symmetra UPS.
Smart-UPS
1. Turn off the equipment that connects to the UPS.
2. Disconnect the UPS from its AC input source.
3. Press the OFF button on the UPS for approximately five
seconds to turn off the DC (battery) power.
Matrix-UPS
1. Turn off the equipment that connects to the UPS.
2. Turn off the circuit breaker on the rear panel of the UPS.
Caution
Damage to the UPS or Management Card can
result if you do not remove all
AC and DC power
from a Smart-UPS or Matrix-UPS model UPS.