Perform a Total Power Off
WARNING: This procedure will disconnect the load.
Note: If shutdown via the display is disabled, then you cannot perform this procedure and
the message: Command not allowed, UPS congured to never shutdown appears. If
you want to enable shutdown via the display, this is done by a Field Service Engineer via
the UPSTuner.
1. Select UPS and press ENTER.
→ UPS Alarm
Power Dist Log
Switch Gear Admin
Environment Help
2. Select UPS Power Control and press ENTER.
→ UPS Power Control
UPS Status
UPS Tests & Diags
UPS Configuration
3. Select Turn UPS Off and press ENTER.
→ Turn UPS Off
Reboot UPS
UPS into Bypass
UPS to Sleep
4. Select No, Don’t Notify to shut down without
delay and press ENTER.
Note: This action will cut all power
to the load without shutting it down
rst. If you want to shut down the
servers rst, then choose Yes, Notify
Servers. Note that this function
is only available for servers with
PowerChute.
Notify PowerChute ?
Cancel
Yes, Notify Servers
→ No, Don't Notify
5. Conrm YES, Turn UPS Off and press
ENTER.
Turn UPS off
Without Server
Notification?
> NO, ABORT
→> YES, Turn UPS Off
6. Wait for the UPS to turn off.
Turning UPS off,
please wait...
8
Symmetra™ PX48, 96, and 160 kW 400 V 100 kW 208 V Operation
990–3015E-001