APC SBP20KRMT4U Switch User Manual


 
SBP20K Series User Manual2
Specifications
Electrical Specifications
Note: The table above represents the electrical ratings of the SBP and not those of the UPS.
UPS wire specifications may vary. The SBP requires a minimum wire size of 25 mm
2
and a
maximum wire size of 50 mm
2
. Refer to the UPS user manual for UPS wiring specifications.
SBP ratings must be equal to or greater than those of the UPS to which it is connected.
The input circuit breaker should not exceed the rating recommended on the UPS.
The system load must not exceed the electrical rating of the UPS. For example, if a 3840 VA
SBP is used with a 3000 VA UPS the maximum load that the system will support is 3000 VA.
Environmental Specifications
Changes and modifications to this unit not expressly approved by APC could
void the warranty.
SBP model Rated Input Voltage Rated Output Voltage
Input Current
maximum
Output Power
Watts/VA
maximum
SBP20KP
200/208/240 VAC
50/60 Hz, 2P+PE
200/208/240 VAC
50/60 Hz, 2P+PE
125 A
each phase
30,000
220/230/240 VAC
50/60 Hz 1P+N+PE
220/230/240 VAC
50/60 Hz, 1P+N+PE
125 A
each phase
30,000
380/400/415 VAC
50/60 Hz, 3P+N+PE
220/230/240 VAC
50/60 Hz, 1P+N+PE
125 A
each phase
30,000
SBP20KRMT4U
200/208/240 VAC
50/60 Hz, 2P+PE
200/208/240 VAC
50/60 Hz, 2P+PE
125 A
each phase
30,000
SBP20KRMI4U
220/230/240 VAC
50/60 Hz, 1P+N+PE
220/230/240 VAC
50/60 Hz, 1P+N+PE
125 A
each phase
30,000
380/400/415 VAC
50/60 Hz, 3P+N+PE
220/230/240 VAC
50/60 Hz, 1P+N+PE
125 A
each phase
30,000
Temperature
Operating 0° to 40° C (32° to 104° F) This unit is intended for indoor use only.
Do not operate the service bypass panel where
there is excessive dust or the temperature or
humidity are outside specified limits.
Be sure the air vents on the SBP are not
blocked. Allow adequate space for proper
ventilation.
Storage -15° to 45° C (-40° to 113° F)
Maximum
Elevation
Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity 0 to 95% relative humidity, non-condensing