SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U12
Maintenance and Transport
Battery replacement
This UPS has a replacable, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical
hazards. Leave the UPS and connected load on during the replacement procedure.
Once the battery modules have been disconnected the connected equipment is not protected from
power outages.
When the battery modules have been replaced the LED on the display interface will prompt the user to
enter a new battery replacement date.
Refer to the appropriate replacement battery user manual for installation instructions. See your dealer or contact
APC at www.apc.com for information on replacement batteries.
Be sure to deliver spent batteries to a recycling facility or ship to APC in the replacement battery
packing material.
Prepare the UPS for transport
1. Disconnect the UPS from all internal and external batteries.
2. Shut down and disconnect all equipment connected to the UPS.
3. Shut down and disconnect the UPS from utility power.
4. Follow shipping instructions outlined in “Service” on page 13 of this manual.
Fault and Overload indicators are illuminated and the UPS emits a sustained alarm tone
The UPS is not sending power to
connected equipment.
Connected equipment exceeds specified “maximum load” as defined in
Specifications on APC Web site, www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from UPS to eliminate overload condition.
The UPS will not provide power from batteries in the event of a utility voltage
interruption.
There is no utility power
There is no utility power and the
UPS is off.
Use the Cold Start feature to supply power to connected equipment from UPS
battery(s).
Press and hold the
ON button. There will be a short beep followed by a longer
beep. Release the button during second beep.
Diagnostic utility voltage feature
All five LEDs are illuminated. The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination. The line voltage is extremely low and should be checked by an electrician.
On Line indicator
There is no LED illumination. The UPS is running on battery, or it must be turned on.
The LED is blinking. The UPS is running an internal self-test.
Problem and Possible Cause Solution