Campbell Manufacturing SDM-SW8A Switch User Manual


 
SDM-SW8A Switch Closure Input
Module
1. Function
The 8 channel SDM-SW8A Switch Closure Input Module (see Figure 1)
measures up to 8 channels of switch closure or voltage pulse inputs. Each
channel may be configured to read single-pole double-throw (SPDT) switch
closure, single-pole single-throw (SPST) switch closure, or voltage pulse.
Output options include counts, duty cycle, and state.
The SW8A is addressed by the datalogger, allowing multiple SW8As to be
connected to one datalogger (refer to Theory of Operation, Section 9). Sixteen
addresses are available, but for most applications, Campbell Scientific, Inc.
recommends no more than 4 SW8As be connected to one datalogger. If more
SW8As are required, please consult Campbell Scientific's Marketing
Department.
In October, 1988, the SDM-SW8A was introduced. Edlog Instruction 102 is
used for communication with the SW8A. CRBasic dataloggers use the
SDMSW8A instruction. Previous to October, 1988, the SDM-SW8 (no "A")
was offered for use only with the CR10, utilizing CR10 I/O Instruction 15.
SDM-SW8As are not compatible with CR10s containing Instruction 15,
and SDM-SW8s are not compatible with CR10s containing Instruction
102. Contact Campbell Scientific's Marketing Department for update options
if incompatibilities exist.
FIGURE 1. SDM-SW8A Front Panel
1