Dell K805N Power Supply User Manual


 
9
Safety Warnings
|
Safety Warnings
CAUTION: Before performing the procedures in this document, read and follow the safety instructions and
important regulatory information in your Safety, Environmental, and Regulatory Information document.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that you should follow during installation and
maintenance of the UPS and batteries. Please read all instructions before operating the equipment and
save this manual for future reference.
DANGER:
Observe the following instruction to help prevent an imminently hazardous situation which, if not
avoided, will result in death or serious injury:
S This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE
PARTS inside the UPS.
WARNING:
Observe the following instructions to help prevent a potentially hazardous situation which, if not
avoided, could result in death or injury:
S Only qualified service personnel (such as a licensed electrician) shall perform the electrical
installation. Risk of electrical shock.
S For UPS models with hardwired input, overcurrent protection for the output AC circuit(s) is to be
provided by others.
S For UPS models with hardwired input, suitably rated disconnect switches for the output AC
circuit(s) are to be provided by others.
S Output overcurrent protection and disconnect switch must be provided by others.
S This UPS contains its own energy source (batteries). The output receptacles may carry live voltage
even when the UPS is not connected to an AC supply.
S Do not remove or unplug the input cord when the UPS is turned on. This removes the safety
ground from the UPS and the equipment connected to the UPS.
S To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection with an ampere rating in accordance with the National Electrical Code
®
(NEC
®
),
ANSI/NFPA 70 or your local electrical code:
UPS Output Power 208V 230V
3750W 30A 25A
4200W 30A 30A
2