Delta Electronics RTU-EN01 Switch User Manual


 
Modbus TCP Remote I/O Communication Module RTU-EN01
DVP-PLC Operation Manual
27
1. Enable:
Decide whether to trigger the RTC in this column.
2. Cyclic:
Decide to trigger the RTC only once, or trigger it on a daily, weekly or monthly basis.
3. Output auto-reset:
After the RTC is triggered, decide whether to retain the output for a period of time and reset the
RTC automatically. R (Coil) will be OFF when the time for reset is reached.
4. Auto-reset time, Unit:
If you select to auto-reset the RTC, the bit device in RTC will retain the output for a period of time.
Range: 1s ~ 24hr.
Range for second as unit: 1 ~ 32,767
Range for minute as unit: 1 ~ 3,600
Range for hour as unit: 1 ~ 24
5. Year, Month, Day, Hour, Minute, Second, Week:
The time to trigger the RTC. If you would like to trigger it only once, only Year, Month, Day, Hour,
Minute and Second need to be set. If you would like to trigger on a daily basis, only Hour, Minute
and Second need to be set. If you would like the RTC to be triggered on a weekly basis, you only
need to set up Week, Hour, Minute and Second. If the RTC is triggered monthly, set up only Day,
Hour, Minute and Second.
6.11 Analog Input/Output Modules
RTU-EN01 offers control registers (CR) for analog I/O modules and is built-in with mapping tables of CR for
read/write. The user can check the CR to be read/written and use Delta’s communication module DVPEN01-SL to
map the CR directly to D registers in DVP-SV series PLC and read/write the D register through PLC program,
controlling the analog I/O module connected to RTU-EN01. RTU-EN01 supports maximum 64 data
reading/writing.
f This function works with DVPEN01-SL of firmware V2.0 or versions above.
Analog I/O modules