Eaton Electrical 0800-7500 Power Supply User Manual


 
22
900 Specifications
* Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown are for the
U.S. and Canada.
** At 0.7 leading or distortion power factor. Size output protection according to all applicable local or national codes.
*** Height includes switch.
Model 0800-2000
2 kVA/1.4 kW
0800-3000
3 kVA/2.1 kW
0800-4500
4.5 kVA/3.2 kW
0800-6000
6 kVA/4.2 kW
0800-7500
7.5 kVA/5.3 kW
AC Input Voltage
and Current
110 = 22 amps
115 = 22 amps
120 = 22 amps
127 = 22 amps
208 = 12 amps
220 = 12 amps
230 = 12 amps
240 = 12 amps
110 = 30 amps
115 = 30 amps
120 = 30 amps
127 = 30 amps
208 = 16 amps
220 = 16 amps
230 = 16 amps
240 = 16 amps
110 = 40 amps
115 = 40 amps
120 = 40 amps
127 = 40 amps
208 = 20 amps
220 = 20 amps
230 = 20 amps
240 = 20 amps
208 = 28 amps
220 = 28 amps
230 = 28 amps
240 = 28 amps
208 = 36 amps
220 = 36 amps
230 = 36 amps
240 = 36 amps
Recommended Input
Service for 60 Hz U.S.
Models*
120 = 30-amp
208 = 15-amp
240 = 15-amp
120 = 40-amp
208 = 20-amp
240 = 20-amp
120 = 50-amp
208 = 25-amp
240 = 25-amp
208 = 35-amp
240 = 35-amp
208 = 45-amp
240 = 45-amp
Output Voltage and
Maximum Output
Current in Amps**
120 = 16 amps
127 = 15 amps
208 = 9 amps
220 = 9 amps
230 = 8 amps
240 = 8 amps
120 = 25 amps
127 = 23 amps
208 = 14 amps
220 = 13 amps
230 = 13 amps
240 = 12 amps
120 = 37 amps
127 = 35 amps
208 = 21 amps
220 = 20 amps
230 =19 amps
240 = 18 amps
120 = 50 amps
127 = 47 amps
208 = 28 amps
220 = 27 amps
230 = 26 amps
240 = 25 amps
120 = 62 amps
127 = 59 amps
208 = 36 amps
220 = 34 amps
230 = 32 amps
240 = 31 amps
Efficiency on AC Line 90% 90% 90% 89% 89%
On Line BTU/hour:
kW/hour:
703
0.206
1024
0.300
1427
0.418
1707
0.500
2116
0.620
Audible Noise (dB) <45 dB <45 dB <45 dB <45 dB <45 dB
Typical Standard
Runtime (minutes)
Full Load:
Half Load:
11 minutes
23 minutes
17 minutes
36 minutes
10 minutes
22 minutes
16 minutes
38 minutes
12 minutes
27 minutes
Weights:
No Internal Bypass,
Standard Batteries:
Internal Bypass,
Standard Batteries:
Battery Cabinet,
Standard Batteries:
FBT21
FBT22
FBT31
FBT32
280 lbs. (127 kg)
303 lbs. (137.4 kg)
235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)
327 lbs. (148.3 kg)
350 lbs. (158.8 kg)
235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)
383 lbs. (173.7 kg)
410 lbs. (186 kg)
235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)
563 lbs. (255.4 kg)
590 lbs. (267.6 kg)
235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)
635 lbs. (288 kg)
662 lbs. (300.3 kg)
235 lbs. (106.6 kg)
355 lbs. (161 kg)
418 lbs. (189.6 kg)
660 lbs. (299.4 kg)
Battery Cabinet
Dimensions (H x W x D)
UPS Dimensions with
Internal Bypass
(H*** x W x D)
UPS Dimensions
(without bypass)
(H x W x D)
28.6 x 13.5 x 35 inches
730 x 345 x 890 mm
27.25 x 13.5 x 28.5 inches
695 x 345 x 725 mm
31.9 x 13.5 x 31.5 in
810 x 347 x 800 mm
30.5 x 13.5 x 25 in
775 x 347 x 635 mm
FBT21, FBT22: 27.25 x 13.5 x 28.5 in. (695 x 345 x 725 mm); add 2.6 in/66 mm to depth for connection box.
FBT31, FBT32: 38.75 x 13.5 x 32.5 in. (985 x 345 x 825 mm); add 2.6 in./66 mm to depth for connection box.
40.1 x 13.5 x 39 inches
1020 x 345 x 990 mm
38.75 x 13.5 x 32.5 inches
985 x 345 x 825 mm