52
Table 11. High-Voltage Model Specifications
Model Number
Power Levels
(Rated at
Nominal Inputs)
AC Input Output on Battery Power
Nominal
Voltage
Voltage
Range
1
Frequency
Range
2
Voltage
3
Frequency
PW5130i1250-XL2U 1250 VA, 1150W
220–240V 160–294V
47–70 Hz (50 Hz
system),
56.5–70 Hz (60 Hz
system)
230V
(+6/-10%)
50/60 Hz
±0.1%
PW5130i1750-XL2U 1750 VA, 1600W
PW5130i2500-XL2U 2500 VA, 2250W
PW5130i3000-XL2U
3000 VA, 2700W
PW5130i3000-XL3U
PW5130G3000-XL2U 3000 VA, 2700W 208V 160–263V
208V
(+6/-10%)
1
The high and low thresholds can be adjusted using the U PS Configuration tool (see page 43).
2
Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
3
Adjustable to 100V (10% derating of output power) 120/127V.
Table 12. Weights and Dimensions
Low-Voltage Model Number Dimensions (WxHxD) Weight
PW5130L1250-XL2U
440×86×509 mm
17.3
×3.4×20.0
24.6 kg (54.3 lb)
PW5130L1750-XL2U 26.3 kg (58.0 l b)
PW5130L2500-XL2U
440×86×634 mm
17.3
×3.4×25.0
34.7 kg (76.4 lb)
PW5130L3000-XL2U 35.3 kg (77.9 l b)
PW5130L3000-XL3U
440×131×484 mm
17.3
×5.2×19.0
33.8 kg (75.5 lb)
High-Voltage Model Number Dimensions (WxHxD) Weight
PW5130i1250-XL2U
440×86×509 mm
17.3
×3.4×20.0
24.3 kg (53.6 lb)
PW5130i1750-XL2U
PW5130i2500-XL2U
440×86×634 mm
17.3
×3.4×25.0
33.8 kg (74.5 lb)
PW5130i3000-XL2U
PW5130G3000-XL2U
440×86×634 mm
17.3
×3.4×25.0
35.3 kg (77.9 lb)
PW5130i3000-XL3U
440×131×484 mm
17.3
×5.2×19.0
34.3 kg (75.6 lb)