SPECIFICATIONS
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide S 164201730 Rev 2
www.powerware.com
55
Table 16. Battery Runtimes
Half Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1250 VA/575W 15 min 22 sec 58 min 1hr40min 2hr23min 3hr5min
1750 VA/800W 9 min 35 sec 36 min 11 sec 1hr2min 1hr29min 1hr55min
2500 VA/1125W 11 min 15 sec 55 min 1hr40min 2hr30min 3hr26min
3000 VA/2700W 10 min 15 sec 44 min 1hr13min 1hr41min 2hr10min
Full Load UPS Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1250 VA/1150W 5 min 29 min 49 sec 54 min 38 sec 1hr19min 1hr44min
1750 VA/1600W 3 min 30 sec 16 min 28 min 30 sec 41 min 53 min 30 sec
2500 VA/2250W 3 min 23 min 42 min 1hr3min 1hr25min
3000 VA/2700W 3 min 17 min 32 min 47 min 1hr2min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.