Eaton Electrical 34003991EN/EB Network Card User Manual


 
Network Management Card
– User Manual 34003991EN/EB Page 114/118
If the Environment Sensor is detected , the following information are managed.
upsmgEnvironAmbientTemp 0.1 degré {8,1,0}
upsmgEnvironAmbientHumidity 0.1 % {8,2,0}
upsmgEnvironmentNum {8,6,0}
upsmgEnvironmentIndex {8,7,1,1,1 }
upsmgEnvironmentComFailure 1(yes) 2(no) {8,7,1,2,1}
upsmgEnvironmentTemperature 0.1 degré {8,7,1,3,1}
upsmgEnvironmentTemperatureLo
w
1(yes) 2(no) {8,7,1,4,1}
upsmgEnvironmentTemperatureHi
gh
1(yes) 2(no) {8,7,1,5,1}
upsmgEnvironmentHumidity 0.1 % {8,7,1,6,1}
upsmgEnvironmentHumidityLow 1(yes) 2(no) {8,7,1,7,1}
upsmgEnvironmentHumidityHigh 1(yes) 2(no) {8,7,1,8,1}
upsmgEnvironmentInput1State closed(1), open(2) {8,7,1,9,1}
upsmgEnvironmentInput2State closed(1), open(2) {8,7,1,10,1}