Emerson 10-30KVA Power Supply User Manual


 
Specifications and Technical Data
62
15 F, P 480 21 30 24 30 208 42 60
15 F, P 600 17 30 19 20 208 42 60
15 F, P 208 49 60 54 60 208 42 60
15 F, P 220 46 60 51 60 208 42 60
15 F, P 240 42 60 47 50 208 42 60
10 F, P 480 14 20 16 20 208 28 40
10 F, P 600 12 15 13 15 208 28 40
10 F, P 208 33 40 36 40 208 28 40
10 F, P 220 31 40 34 40 208 28 40
10 F, P 240 29 40 32 40 208 28 40
Table 31 Multi-module bypass cabinet electrical data
System
Size Type kVA
System
I/P Voltage
(VAC)
System
Max Input
Current
System
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)
1+1
A00, BR0
30 208 104 125 208 83 125
20 208 70 90 208 56 70
15 208 53 70 208 42 60
10 208 35 45 208 28 40
CR1 30 208 107 150A 208 83 125
CR1, DR1 30 220 101 150A 208 83 125
CR1, DR1 30 480 46 70A 208 83 125
CR1, DR1 30 600 37 60A 208 83 125
CR1 20 208 71 100A 208 56 70
CR1, DR1 20 220 68 100A 208 56 70
CR1, DR1 20 480 31 50A 208 56 70
CR1, DR1 20 600 25 40A 208 56 70
CR1 15 208 54 80A 208 42 60
CR1, DR1 15 220 51 80A 208 42 60
CR1, DR1 15 480 23 40A 208 42 60
CR1, DR1 15 600 19 30A 208 42 60
CR1 10 208 36 60A 208 28 40
CR1, DR1 10 220 34 50A 208 28 40
CR1, DR1 10 480 16 30A 208 28 40
CR1, DR1 10 600 12 20A 208 28 40
Table 30 Maintenance bypass cabinet electrical data (dual input)
kVA Type
System
I/P Voltage
(VAC)
Rectifier
Max Input
Current
Rectifier
Input OCP
CB Size (A)
Bypass
Max Input
Current
Bypass
Input OCP
CB Size (A)
O/P Voltage
(VAC)
Nominal O/P
Current Rating (A)
Output OCP
CB Size (A)