Emerson 115-120 Power Supply User Manual


 
Specifications and Technical Data
103
11.0 SPECIFICATIONS AND TECHNICAL DATA
11.1 Conformity and Standards
The Liebert
®
APM
has been designed to conform to the following standards:
The Liebert APM has UL and c-UL approval.
11.2 UPS Environmental
The Liebert APM is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Safety UL 1778, CSA 22.2 107.3, 4th Edition
Surge ANSI 62.41 Cat A3 and B3
Harmonics IEC 61000-3-4
Electrical Fast Transient IEC 61000-4-4 Level 4, Criteria A
ESD IEC 61000-4-2 Level 4, Criteria A
FCC Part 15, Class A
Radiated Immunity IEC 61000-4-3 Level 3, Criteria A
Conducted Immunity IEC 61000-4-6 Level 4, Criteria A
Low-Frequency Signals IEC 61000-2-2 Criteria A
Transportation ISTA Procedure 1H
ISO 9001
Misc OSHA, ASME, NEMA PE-1
Table 33 Environmental requirements
Item Requirements
Acoustical Noise, dBA, at 55 in. (1.4m) 57 (45kVA); 60 (90kVA)
With Top Fan Kit 69 (45kVA); 70 (90kVA)
Operating Altitude
3300 ft. (1000m) above sea level; derate power by 1% per 330 ft.
(100m) between 3300 and 6000 ft. (1000m and 2000m)
Relative Humidity 0 to 95% non condensing
Operating Temperature, °F (°C)
32 to 104 (0 to 40)*
Battery life is halved for every 18°F (10°C) increase above 68 (20)
UPS Storage/Transport Temperature, °F (°C) -4 to 158 (-20 to 70)
Recommended Battery Storage
Temperature, °F (°C)
-4 to 86 (-20 to 30)
68 (20) for optimum battery storage
Table 34 UPS mechanical characteristics
Rated Power, kVA
15 - 90
Dimensions, W x D x H, in (mm) 31-1/2 x 39-1/2 x 78-3/4 (800 x 1000 x 2000)
Weight, without batteries, lb (kg) 1100 (500)
Color Black
Protection Degree IEC (60529) IP20 (finger-proof with front doors open or closed)