Emerson 115-50/60HZ Power Supply User Manual


 
Installation Drawings
62
Figure 39 Outline drawing, Liebert BDC for Liebert
®
APM
, 15-45kVA
Figure 40 Outline drawing, Liebert BDC for Liebert APM, 15-90kVA
6.3" (159)
Outside Panel
Cable EntryArea
11.4" x 13.2"
(290 x 335mm)
Cable EntryArea
11.4" x 13.2"
(290 x 335mm)
6.5" (164)
Outside Panel
6.7" (169)
Outside Panel
6.4" (162)
Outside Panel
23.7"
(602)
34.6"
(879mm)
28.3"
(719)
Bracket
Centers
5.5" (140)
23.6" (600)
Center
of
Gravity
Leveling
Feet
RIGHT SIDE
UAM06008
Rev. 4
FRONT
78.7"
(2000mm)
TOP
Maximum Door
Swing: 120°
NOTES
1. All dimensions are in inches [mm].
2. 24" (610mm) minimum clearance above unit and
36" (914mm) front access required for service.
3. Keep cabinet within 15° of vertical.
4. Top and bottom cable entryavailable through removable
access plates. Remove, punch to suit conduit size and replace.
5. Control wiring and power wiring must be run
in separate conduits.
6. Copper cables only are recommended.
7. All wiring is to be in accordance with national
and local electrical codes.
BOTTOM
X
Z
39.5" (1000)
24" (609)
Liebert BDC
with Distribution Type
Dimension, in. (mm)
Weight,*
lb (kg)XYZ
Without Panelboard 11.8" (300)
39.4"
(1000)
14.9" (379) 525 (239)
With Panelboard 11.8" (300)
39.4"
(1000)
14.9" (379) 625 (284)
* Shipping weight, add 150lb. (68kg)
6.3" (159)
Outside Panel
Cable EntryArea
11.4" x 13.2"
(290 x 335mm)
Cable EntryArea
11.4" x 13.2"
(290 x 335mm)
6.5" (164)
Outside Panel
6.7" (169)
Outside Panel
6.4" (162)
Outside Panel
23.7"
(602)
34.6"
(879mm)
28.3"
(719)
Bracket
Centers
5.5" (140)
23.6" (600)
24" (609)
X
Y
Center
of
Gravity
Leveling
Feet
UAM06010
Rev. 4
BOTTOM
RIGHT SIDE
FRONT
78.7"
(2000mm)
TOP
Maximum Door
Swing: 120°
z
39.5" (1000)
NOTES
1.All dimensions are in inches [mm].
2. 24" (610mm) minimum clearance above unit and
36" (914mm) front access required for service.
3. Keep cabinet within 15° of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove, punch to
suit conduit size and replace.
5. Control wiring and power wiring must be run
in separate conduits.
6. Copper cables only are recommended.
7.All wiring is to be in accordance with national
and local electrical codes.
Liebert BDC with Distribution Type
Dimension, in. (mm)
Weight,* lb (kg)XYZ
No Distribution 11.8" (300) 39.4" (1000) 14.9" (379) 550 (250)
With 2-225A Subfeed Breakers 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
With 400A Panelboard 11.8" (300) 39.4" (1000) 14.9" (379) 660 (300)
* Shipping weight, add 150lb. (68kg)
No Distribution With 480V Transformer 11 8" (300) 32 7" (830) 24 8" (630) 1522 (692)