Emerson 250-400kVA Power Supply User Manual


 
SPECIFICATIONS
41
System Parameter
UPS Efficiency AC-AC 100% Load, % 93.9% 94% 94.2%
UPS Efficiency AC-AC 50% Load, % 93.2% 93.3% 93.4%
Physical Parameters & Standards, in (mm)
Width 71.8 (1823) 78.5(1993) 78.5(1993)
Depth 33.5 (850) 33.5 (850) 39.4 (1000)
Height 76.8 (1950)
Weight, lb (kg) approx. 4165 (1889) 4890 (2218) 5450 (2472)
Color Charcoal (ZP-0420)
Front Door Opening (for serviceability) More than 180°
Degree of Protection for UPS Enclosure IP 20 (with and without front door open)
Standards & Conformities
UL 1778
CSA 22.2 107.3
FCC Part 15, Class A
IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A
EN61000-4-6, Level 4, Criteria A
EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3 ISTA Procedure 1H
WEEE
Table 6 Electrical specifications (continued)
Liebert NXL Model Size 250 300 400