86
Site Planning Data 600VAC Input
UPS
Rating AC Voltage
Standard AC Input
without Filter
AC Input with Filter
Option
AC Output
Current
Max. Max. Heat Approx.
Concen-
trated
kVA kW Input Output Nom Max
Recom-
mended
OPCD
Nom Max
Recom-
mended
OCPD
Nom
Recom-
mended
OCPD
Battery
KW
Battery
Disch.
(Amps)
Dissipation
BTU/hr
Full Load
Dimensions
WxDxH
(Inches)
Unpacked
Weight
(Pounds)
Floor
Loading
(Lb/SqFt)
Cooling
Air
(CFM)
30 24 600 208 32 40 50 28 34 50 83 125 26 66A 8,500
31.7x32.5x71
2,200 307 720
30 24 600 600 32 40 50 28 34 50 29 50 26 66A 8,500
31.7x32.5x71
2,200 307 720
40 32 600 208 42 53 60 37 46 60 111 150 34 88A 11,000
31.7x32.5x71
2,200 307 720
40 32 600 600 42 53 60 37 46 60 38 50 34 88A 11,000
31.7x32.5x71
2,200 307 720
50 40 600 208 53 66 70 46 57 70 139 175 43 109A 14,000
31.7x32.5x71
2,100 307 720
50 40 600 600 53 66 70 46 57 70 48 60 43 109A 14,000
31.7x32.5x71
1,900 307 720
65 52 600 208 67 84 100 59 74 100 180 225 55 141A 18,000
39.4x32.5x71
2,200 304 960
65 52 600 600 67 84 100 59 74 100 63 80 55 141A 18,000
39.4x32.5x71
2,100 304 960
80 64 600 208 83 103 125 73 91 125 222 300 68 174A 22,000
39.4x32.5x71
1,900 304 960
80 64 600 600 83 103 125 73 91 125 77 100 68 174A 22,000
39.4x32.5x71
2,700 304 960
100 80 600 208 103 128 175 90 113 150 278 350 85 218A 26,000 49.2x32.5x71 2,500 342 1440
100 80 600 600 103 128 175 90 113 150 96 125 85 218A 26,000 49.2x32.5x71 2,300 342 1440
130 104 600 208 133 167 200 118 147 200 361 450 111 283A 33,000 49.2x32.5x71 2,700 342 1440
130 104 600 600 133 167 200 118 147 200 125 175 111 283A 33,000 49.2x32.5x71 2,500 342 1440
Notes: — 1,3,4,5,7,8, 9,11,12, 13 2,3,5,7,8,9,11,12 6,8,9,11,12 14 14 — —