87
Site Planning Data 220 OR 240 VAC INPUT
UPS
Rating AC Voltage
Standard AC Input
without Filter
AC Input with Filter
Option
AC Output
Current
Max. Max. Heat Approx.
Concen-
trated
kVA kW Input Output Nom Max
Recom-
mended
OPCD
Nom Max
Recom-
mended
OCPD
Nom
Rec.
OCPD
Battery
KW
Battery
Disch.
(Amps)
Dissipation
BTU/hr
Full Load
Dimensions
WxDxH
(Inches)
Unpacked
Weight
(Pounds)
Floor
Loading
(Lb/SqFt)
Cooling
Air
(CFM)
30 24 220 208 87 108 150 75 94 125 83
125 26 66A 8,500 31.7x32.5x71 2,200 307 720
30 24 220 220 87 108 150 75 94 125
79 100 26 66A 8,500 31.7x32.5x71 2,200 307 720
30 24 240 208 79 99 125 69 86 125 83
125 26 66A 8,500 31.7x32.5x71 2,200 307 720
30 24 240 240 79 99 125 69 86 125 72
100 26 66A 8,500 31.7x32.5x71 2,200 307 720
40 32 220 208 115 144 175 100 125 150 111 150 34 88A 11,000
31.7x32.5x71 2,200 307 720
40 32 220 220 115 144 175 100 125 150 105 150 34 88A 11,000
31.7x32.5x71 2,200 307 720
40 32 240 208 106 132 175 92 115 150 111 150 34 88A 11,000
31.7x32.5x71 2,200 307 720
40 32 240 240 106 132 175 92 115 150 96 125 34 88A 11,000
31.7x32.5x71 2,200 307 720
50 40 220 208 144 180 225 125 157 200 139 175 43 109A 14,000
31.7x32.5x71 2,200 307 720
50 40 220 220 144 180 225 125 157 200 131 175 43 109A 14,000
31.7x32.5x71 2,200 307 720
50 40 240 208 132 165 200 115 144 175 139 175 43 109A 14,000
31.7x32.5x71 2,200 307 960
50 40 240 240 132 165 200 115 144 175 120 150 43 109A 14,000
31.7x32.5x71 2,200 307 960
65 52 220 208 183 229 300 161 202 250 180 225 55 141A 18,000 39.4x32.5x71 2,700 304 960
65 52 220 220 183 229 300 161 202 250 171 225 55 141A 18,000 39.4x32.5x71 2,700 304 960
65 52 240 208 168 210 250 148 185 225 180 225 55 141A 18,000 39.4x32.5x71 2,700 304 960
65 52 240 240 168 210 250 148 185 225 156 200 55 141A 18,000 39.4x32.5x71 2,700 304 960
80 64 220 208 225 281 350 198 248 300 222 300 68 174A 22,000 39.4x32.5x71 2,700 304 960
80 64 220 220 225 281 350 198 248 300 210 300 68 174A 22,000 39.4x32.5x71 2,700 304 960
80 64 240 208 206 258 350 182 227 300 222 300 68 174A 22,000 39.4x32.5x71 2,700 304 960
80 64 240 240 206 258 350 182 227 300 192 250 68 174A 22,000 39.4x32.5x71 2,700 304 960
100 80 220 208 280 350 450 247 308 400 278 350 85 218A 26,000 49.2x32.5x71 3,800 342 1440
100 80 220 220 280 350 450 247 308 400 262 350 85 218A 26,000 49.2x32.5x71 3,800 342 1440
100 80 240 208 256 321 400 226 283 350 278 350 85 218A 26,000 49.2x32.5x71 3,800 342 1440
100 80 240 240 256 321 400 226 283 350 241 300 85 218A 26,000 49.2x32.5x71 3,800 342 1440
130 104 220 208 364 455 600 321 401 500 361 450 111 283A 22,000 49.2x32.5x71 3,800 342 1440
130 104 220 220 364 455 600 321 401 500 341 450 111 283A 22,000 49.2x32.5x71 3,800 342 1440
130 104 240 208 333 417 500 294 368 450 361 450 111 283A 22,000 49.2x32.5x71 3,800 342 1440
130 104 240 240 333 417 500 294 368 450 313 400 111 283A 22,000 49.2x32.5x71 3,800 342 1440
Notes: — 1,3,4,5,7,8, 9,11,12, 13 2,3,5,7,8,9,11,12 6,8,9,11,12 14 14 — —