Emerson 30-130 kVA Power Supply User Manual


 
34 Installation Drawings
Figure 15 Outline Drawing, Battery Power Pack, 49-Inch Cabinet
FRONT VIEW
FRONT VIEW
WITH DOORS REMOVED
DETAIL FOR DC BUS BARS
SIDE VIEW
WITH COVER REMOVED
CIRCUIT
BREAKER
BOTTOM VIEW
CASTER CENTERS
AIR EXHAUST
CUTOUT
6 PLACES
TOP VIEW
MAX DOOR SWING 120°- LIFT OFF DOORS
BATTERIES
CONDUIT ENTRY
5.5 X 11.0
TOP AND BOTTOM
DC BUS BARS
HANDLING.
11. APPROX WEIGHT OF CABINET IS 3500 TO 5100 LBS.
FORKLIFT HANDLING.
10. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR
9. COLOR - IBM OFF WHITE.
68°F-77°F (20°C-25°C).
8. RECOMMENDED OPERATING TEMPERATURE RANGE:
NATIONAL AND LOCAL ELECTRICAL CODES.
7. ALL WIRING IS TO BE IN ACCORDANCE WITH
NOT RECOMMENDED.
6. ALUMINUM AND COPPER CLAD ALUMINUM CABLES ARE
IN SEPARATE CONDUIT.
5. CONTROL WIRING AND POWER WIRING MUST BE RUN
PUNCH TO SUIT CONDUIT SIZE, AND REPLACE.
REMOVABLE TOP AND BOTTOM ACCESS PLATES. REMOVE,
4. EXTERIOR CABLE ENTRY AVAILABLE THROUGH
3. KEEP CABINET WITHIN 15° OF VERTICAL WHILE
AT TOP FOR AIR EXHAUST.
2. MIN CLEARANCE 36 INCHES IN FRONT, 12 INCHES
1. ALL DIMENSIONS ARE IN INCHES.
13. EACH MOUNTING LOCATION IS SUPPORTED
BY (2) 10 GA. (.135") GALVANIZED STEEL. THE
THREADED 12MM INSERT IS APPROX. 3/4" DEEP.
12. THREADED MOUNTING HOLES USED FOR SEISMIC
ANCHORING OR FLOORSTAND. NOTE, IF FLOORSTAND
IS USED THE WEIGHT OF THE UNIT MUST BE
SUPPORTED UNDER ALL CASTERS.
MOUNTING BOLTS MUST BE THREADED INTO UNIT
MOUNTING HOLES FROM UNDERNEATH UNIT BASE.
BUS BARS
MOTOR
OPERATOR
OPTIONAL
CIRCUIT
BREAKER
APPROX AREA
CONTROL AND
SIDE ACCESS
POWER WIRE
4.56 x 2.25
(BOTH SIDES)
NOTES:
V CARMONA
REF. DWG.
DRAWN BY
CHK BY
OUTLINE DRAWING
49" BATTERY CABINET
NPOWER
1050 DEARBORN DRIVE,
COLUMBUS, OHIO 43229
1/22/033
FILE NAME: Batts\UBC11003-03
REV. NO.
DWG. NO.
UBC11003
DATE
FRONT
SUPPORT TRAY &
SUPPORT BRACKET
(SEE NOTE 15)
POSITION SUPPORT TRAY AND ATTACH TO CABINET. THEN
15. "BEFORE SLIDING OUT BATTERIES ON BATTERY TRAY"
14. REFER TO DETAIL A FOR DIMENSION TO FRAME
REMOVED BETWEEN ADJACENT UNITS WHICH ARE
BOLTED TOGETHER.
WITH SIDE PANEL REMOVED. SIDE PANELS ARE
SECURE (2) SUPPORT BRACKETS TO THE SUPPORT TRAY
DETAIL A
WITHOUT SIDE PANEL
REAR OF UNIT SHOWN
2.72
MOUNTING HOLE
12MM THREADED
LEVELER
CENTER
GRAVITY
CENTER
GRAVITY
12mm DIA. THREADED
MOUNTING HOLE (6) TYP.
(SEE NOTES 12 & 13)
(SEE DETAIL A)
CASTER
CENTERS
12MM
12MM CENTERS
CENTERS
AND TO THE CABINET. REFER TO THE APPROPRIATE LIEBERT
USERS MANUAL FOR FURTHER DESCRIPTION & DETAILS.