7000 Seri es ATB
Automatic Transfer &
Bypass–Isolation Switches
F–design, 3000 and 4000 amp. sizes
TABLE OF CONTENTS
section-page
INSTALLATION 1-1........................
Mounting 1-1.............................
Power Connections 1-2....................
Engine Starting & Auxiliary Circuits 1-2......
Functional Test 1-5, 1-6, 1–7................
TESTING & SERVICE 2-1..................
Transfer Test 2-1..........................
Preventive Maintenance 2-1................
Disconnecting the Controller 2-1............
Manual Load Transfer 2-2..................
Trouble-Shooting 2-2......................
BYPASSING & ISOLATING 3-1..............
Bypassing the ATS 3-1....................
Isolating the ATS 3-1......................
Return to Service 3-3......................
INDEX back cover.........................
An experienced licensed electrician must install ATB
Refer to the outline and wiring drawings provided
with your 7000 Series ATB for all installation and
connection details and accessories.
Refer to Group 5 Controller User’s Guide 381333–126
for ATS status display messages, time delay s, pickup
& dropout settings, and adjustments.
Rating Label
Each 7000 Series ATB c ontains a rating label to define the
lo ads and fault cir c u it withs tan d/c l os in g rating s. Refer to the
label on the Transfer Switch for s pecific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
!
Namepl ate
The Transfer Switch nameplate includes data for each
specific 7000 Series ATB. Use the switch only within the
limits shown on this nameplate. A typical Catalog Number
is shown below with its elements explained:
Catalog Number Identification
Typical 7000 Series ATB catalog no. for overlapping neutral, 3 pole, 4000 amp, 480 V, in Type 1 enclosure:
7A TB C 3 4000 N 5 C
Phase Poles
Neutral
A –solid
Amperes Voltage Controller Enclosure
5X – if accesso-
ries ordered
5 –standard
G –type4
C –type1
F –type3R
L –type12
3 –threeØ
2 –singl
B 120
D 220
A 115
C 208
E 230
K 415
M 460
J 400
L 440
N 480
G 277
F 240
H 380
Q 575
P 550
R 600
4000
3000
blank --- none
blank – open type
C – overlapping