69
25A Switch Mode RectifierNT5C06B / C Installation and User Manual
Low voltage disconnect
The LVD protects the batteries. The LVD disconnects the load from the
batteries when a preset low voltage, which can cause permanent battery
damage, is reached.
The LVD is available in brown or grey (faceplate only). The nominal
dimensions are 6.60 inches high, 10.25 inches deep, and 2.2 inches or 5.85
inches wide. The LVD is designed to be housed in the power shelf and is
used primarily in embedded applications.
The Low Voltage and Low Voltage Disconnect alarms are visually displayed
on the LVD unit and can also be monitored externally.
Electrical
- Input voltage: -42 to -60 V DC
- Input current: 0.400 A
- LVD current capacity 50 A
- LVD range -42 to -53 V DC
- Auto reconnect 8 V above the release level
Environmental
The LVD will operate satisfactorily under the following conditions:
- Temperature: -40°C to 65°C (-40°F to 149°F)
- Humidity: 0% to 95% (non condensing)
- Altitude: Sea level to 2100m (7000 ft.)
Storage
During shipping and storage the unit can withstand the temperature and
humidity levels specified below:
- High temperature: +75°C Dry heat (167°F)
- Low temperature: -50°C (-58°F)
- Humidity 0 to 95% (non condensing)