Emerson Process Management MSL600 Computer Monitor User Manual


 
Page 33
MSL600
Installation, Operation & Maintenance Manual
IP262/Z0, Rev. AB
February 2012
7.6.1.2 Fault mode (relay RL1 and RL2 parameters P560 to P570)
There are several fault conditions which can be assigned to a relay. Fault conditions may be selected to be
signalled by relay, current, both relay and current, or not at all.
Messages describing active faults are automatically written to the lower HMI display.
When a fault condition occurs, a relay configured in fault mode will de-energise. Fault conditions are listed
below:
x Memory Fault - P560
A memory fault occurs if system memory has been corrupted. On occasion the control unit may indicate a
memory fault when first powered up. This is normal because the unit is automatically loading default
settings in to the memory. After the first power up this fault message should not occur again. All control
units are first powered up prior to leaving the factory. If the memory fault message appears after the unit
has been switched on and off at least once then consult the factory.
x CU Temp Fault - P561
A fault is indicated if the temperature within the control unit exceeds pre-set limits.
x Xdr Temp Fault - P563
A fault is indicated if the temperature within the transducer unit exceeds pre-set limits.
7.6.1.3 Set point mode (relay RL1 and RL2)
The relays can be operated in set point mode. See also section 7.6.2.
For example:
If it is required to turn a pump on using relay 1 when the sludge blanket reaches a depth of 3.5m (11.5 ft), then
3.5 (11.5) is programmed in to P411 (RL1 on point).
Note:
It is advisable that the "On" and "Off" points are always set to different values, nominally 50mm (2 in/0.16ft)
apart.
7.6.1.4 De-sludge mode (relay RL1 and RL2)
The relay can be programmed to operate in de-sludge mode. The de-sludge parameters are described in
section 7.3 of the manual.
7.6.1.5 On mode (relay RL1 and RL2)
The relays can be switched permanently on if required.
7.6.1.6 Off mode (relay RL1 and RL2)
The relays can be switched permanently off if required.
7.6.1.7 None mode (relay RL1 and RL2)
If the relay mode is set to "None" then the relay remains in its last valid state i.e. if the relay is "On" and the
mode is changed to "None", the relay remains "On".
7.6.1.8 Sludge Level Limits mode (relay RL1 and RL2)
If the relay mode is set to Slg Lev Limits, the relay is energised above the Relay On point. It is also energised
below the Relay Off point. However, the relay is de-energised in between the "On" and "Off" points.
7.6.1.9 Temperature Over Limits mode (relay RL1 and RL2)
If the relay mode is set to Temp OL, the relay is energised above the minimum and maximum control unit
operating temperatures. The relay is de-energised while temperatures are within the normal operating range.