CrossPoint / MAV Matrix Switchers • Remote Control
Remote Control
CrossPoint / MAV Matrix Switchers • Remote Control
4-2
Refer also to the CrossPoint 450 Plus / MAV Plus User’s Manual at www.extron.com.
4-3
Refer also to the CrossPoint 450 Plus / MAV Plus User’s Manual at www.extron.com.
Selected SIS Commands
The switchers have Simple Instruction Set (SIS
™
) commands that
you can use for operation and configuration. You can run these
commands from a PC connected to either of the switcher’s serial
ports or the Ethernet port. See g (page 2-4), h (page 2-5), and
l (page 2-6), for connection information.
Establishing a network (Ethernet) connection
N
If you connect to the switcher via the LAN port, and it
is the first time you have done so, you may change the
controller’s default settings (IP address, subnet mask,
and [optional] administrator name and password). See
"Configuring for Network Communication" for details.
Establish a network connection as follows:
1. Open a TCP socket to port 23 using the switcher’s IP
address.
N
The factory default IP address is 192.168.254.254.
The switcher responds with a copyright message including
the date, the name of the product, the firmware version,
the part number, and the current date/time.
N
If the switcher is not password-protected, the device is now
ready to accept SIS commands.
N
If the switcher is password-protected, a password
prompt appears.
2. If the switcher is password protected, enter the appropriate
password.
If the password is accepted, the switcher responds with
Login User or Login Administrator.
If the password is not accepted, the Password prompt
reappears.
Connection timeouts
The Ethernet link times out and disconnects after a designated
period of time of no communications. By default, this timeout
value is set to five minutes but the value can be changed. See
the Set Connection Timeout command on page 4-9.
N
Extron recommends leaving the default timeout at five
minutes and periodically issuing the Query (Q) command
to keep the connection active or disconnecting the socket
and reopening the connection when necessary.
Number of connections
A switcher can have up to 200 simultaneous TCP connections,
including all HTTP sockets and Telnet connections. When
the connection limit is reached, the switcher accepts no new
connections until some have been closed. No error message or
indication is given that the connection limit has been reached.
To maximize performance of your switcher, the number of
connections should stay low and unnecessary open sockets
should be closed.
Verbose mode
Telnet connections to a switcher can be used to monitor
for changes that occur on the switcher, such as front panel
operations and SIS commands from other Telnet sockets or a
serial port. For a Telnet session to receive change notices from
the switcher, the Telnet session must be in verbose mode 3. See
the Verbose Mode command on page 4-9. In verbose mode 3,
the Telnet socket reports changes in messages that resemble SIS
command responses.
Host-to-switcher instructions
The switcher accepts SIS (Simple Instruction Set) commands
through either serial port. SIS commands consist of one or more
characters per command field. They do not require any special
characters to begin or end the command character sequence.
Each switcher response to an SIS command ends with a carriage
return and a line feed (CR/LF =
]
), which signals the end of
the response character string. A string is one or more characters.
N
The table that begins on the next page is a partial list
of SIS commands. For a complete listing, refer to the
CrossPoint 450 Plus / MAV Plus Switcher User's
Manual, chapter 4, “Programmer’s Guide”.