Falcon XG2.2K-1T Power Supply User Manual


 
29
Model Number XG2.2K-1T XG3K-1T
Model Rating 2200VA/1540W 3000VA/2100W
DIMENSIONS
Unit
W x D x H in. (mm)
16.8 x 21.5 x 3.5 (2U)
(426 x 546 x88)
16.8 x 21.5 x 3.5 (2U)
(426 x 546 x 88)
Shipping
W x D x H in. (mm)
22 x 25.75 x 8.5
(560 x 654 x 215)
22 x 25.75 x 8.5
(560 x 654 x 215)
WEIGHT
Unit lbs (kg) 63.9 (29) 66.2 (30)
Shipping lbs (kg) 87.1 (39.5) 89.3 (40.5)
INPUT
Voltage Range 120 VAC nominal; variable based on output load
80 – 138 VAC full load,
60 – 138 VAC 25% load, without using battery
Frequency 45 – 65 Hz auto sensing
Power Factor >0.98 at full load
Current Harmonics < 9% at full load
Protection Fuse
Power Cord 6 ft. attached with
NEMA L5-20 plug
6 ft. attached with
NEMA L5-30 plug
OUTPUT
Output Receptacles (4) NEMA 5-15R
(1) L5-30R & 1) 5-15
(4) NEMA 5-15R or
(1) L5-30R & 1) 5-15R
Voltage 100/110/115/120 (user configurable) VAC
Voltage Regulation + 2% of nominal
Frequency 60 Hz
Waveform/Distortion Sinewave/ THD < 3% @ full linear load
Overload 100~110% for 120 seconds,
111~150% for 20 seconds,
151% immediately, transfer to bypass within 4 ms
Short Circuit Protection 15A Fuse for per 2 output outlets
BATTERY MODULE ( 1each Standard with 2.2 & 3kVA UPS)
Back-up time See Battery Run Time charts
DIMENSIONS
Unit
W x D x H in. (mm)
16.8 x 21.5 x 3.5
(426 x 546 x 88.9)
Shipping
W x D x H in. (mm)
25.75 x 21.5 x 8.5
(654 x 546 x 215)
WEIGHT
Unit lbs (kg) 62 (28)
Shipping lbs (kg) 78 (35.3)
Packs 2 x 48 VDC packs per module (2)( PN BA04009
Battery Type Sealed Lead Acid, Valve-regulated, Rechargeable