Appendix B. Driver Error Messages.
Message Description
FCI_E3:#1 FYI. Use a DA called <%s> to expose
diagnostic info., FCI_E3_STATS_DA )
Refer to Appendix B.1
FCI_E3:#2 FYI. Added Event Desc=<%s> Index=%d
Categ=%d , new_event_desc ,
new_event_desc_index_value , new_event_desc_categ ) ;
Printed for information only. No action
required if it confirms your expectations.
FCI_E3:#3 Err. No space. Reject Event Desc=<%s>
Index=%d , new_event_desc ,
new_event_desc_index_value ) ;
There is only space for 60 event types.
4
FCI_E3:#4 FYI. Duplicate Event Desc=<%s>. ,
new_event_desc ) ;
FCI_E3:#5 FYI. Duplicate Event Desc=<%s>. ,
new_event_desc ) ;
The Event type being added already
exists. If you are updating the category,
ignore the message. Otherwise correct the
configuration file.
4
FCI_E3:#6 Err. Event Index=%d. Too big to set bit.,
drv_bd->event_index )
If the event index is greater than 64 then
the data cannot be stored as bits - only 64
bits are reserved for events.
FCI_E3:#7a Err. DA=%s too short. Rqd=%d, dt-
>buffer_name , offset );
FCI_E3:#7b Err. DA=%s too short. Rqd=%d, possible_md-
>data->buffer_name , offset );
The MD in question has a length and
offset which makes it run past the end of
the Data Array. Message 7b is printed
when data is being stored as bits.
4
FCI_E3:#8 FYI. Reset was rcvd and processed! Stamped
%s %s , drv_bd->time , drv_bd->date )
Printed for information only. No action
required.
FCI_E3:#9 Err. Reset was ignored.
A reset was received but the driver could
not reset any data. 'Clear_on_Reset'
possibly set to 'no' on all Map Descriptors?
FCI_E3:#10 FYI. Reset of DA=%s Off=%d Len=%d,
possible_md->data->buffer_name , possible_md-
>bxi_data_buffer_offset , possible_md->data_length );
Printed for information only. No action
required.
FCI_E3:#11 Err. Cant reset DA=%s len=%d rqd=%d,
possible_md->data->buffer_nam
e ,
da_get_length_in_items ( (DAH_TYP) possible_md->data )
, possible_md->data_length+possible_md-
>bxi_data_buffer_offset );
The Map Descriptor in question has a
length and offset which makes it run past
the end of the Data Array.
4
FCI_E3:#12a Err. No MD's to store message data.
FCI_E3:#12b Err. No MD's to store message data."
FCI_E3:#13 Err. Msg was ignored. MD Required for
Storage.
The Driver could not find a place to store
data from a message received. If the data
is not required then the message may be
ignored. Otherwise update the
configuration file
4
.
FCI_E3:#13a Err. Diagnostic 1);
FCI_E3:#13b Err. Diagnostic 2);
FCI_E3:#13c Err. Diagnostic 3);
Take a log. Try and repeat the event that
caused the message to be printed. Then
contact tech support.
FCI_E3:#14 Err. <%s> file not found., md-
>mapdesc_name ) ;
FCI_E3:#15 Err. Event Type=<%s> Not recognized." ,
drv_bd->event_desc )
FCI_E3:#16 Err. Point Type='%c'(%#x) Not recognized. ,
drv_bd->point_identifier[0] , drv_bd->point_identifier[0] ) ;
If this error is repeated often it is possible
that a FCI firmware update has made the
driver unusable. Take a log and contact
tech support.
4
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to
take effect.