FieldServer FCI E3 Series Computer Drive User Manual


 
FS-8700-132 Gamewell FCI-E3 Driver Manual Page 18 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Message Description
FCI_E3:#17 Err. Loop=%d < 1. Rejected. , drv_bd->loop )
This message should only be printed if a
byte in a message has been corrupted. If
you notice it more than once then take a
log and contact tech support.
FCI_E3:#18 Err. Loop Type='%c'(%#x) Not recognized. ,
drv_bd->point_identifier[2] , drv_bd->point_identifier[2] )
If this error is repeated often it is possible
that a FCI firmware update has made the
driver unusable. Take a log and contact
tech support.
FCI_E3:#19 Err. Relay=%d < 1. Rejected. , drv_bd->relay
FCI_E3:#20 Err. Zone=%d < 1. Rejected. , drv_bd->zone"
This message should only be printed if a
byte in a message has been corrupted. If
you notice it more than once then take a
log and contact tech support.
FCI_E3:#21 Err. Point Type not recognized
FCI_E3:#22 Err. Undefined Point Type"
Valid Point Types are listed in section
4.4.2
5
FCI_E3:#23 Err. Event Type not recognized
FCI_E3:#24 Err. Undefined Event Type
Valid Event Types are listed in section
4.4.2
5
FCI_E3:#25a Err. Address+Length>99. Length Truncated
FCI_E3:#25b Err. Address+Length>99. Length Truncated
The maximum value for a sensor/module
is 99. The combination of address and
length specified produce a number > 99
5
FCI_E3:#26 Err. Invalid Module number. Expected 1..99
FCI_E3:#27a Err. Invalid Loop number. Expected 1..10
FCI_E3:#27b Err. Invalid Loop number. Expected 1..10
FCI_E3:#27c Err. Invalid Loop number. Expected 1..10
FCI_E3:#28 Err. Invalid Sensor number. Expected 1..99
FCI_E3:#29 Err. Invalid Zone number. Expected 1..255
FCI_E3:#30 Err. Invalid Relay number. Expected 1..255
Correct the configuration file
5
FCI_E3:#31 Err. Point Type Invalid.
Valid Point Types are listed in Section
4.4.2
5
FCI_E3:#32 Err. No MD Length. Default to 1
The length of each Map Descriptor should
be specified. Refer to Section 4.4.2
5
FCI_E3:#33 Err. Driver can’t poll or write.
The driver can only listen passively for
message from the panel. Map Descriptors
may not be configured as active.
5
FCI_E3:#36 Err. Too Short. Bytes=%d , conn->ux_iptr"
An event message is less than 80 bytes
long. If this error is repeated often it is
possible that a FCI firmware update has
made the driver unusable. Take a log and
contact tech support.
5
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to
take effect.