FieldServer NCA2-NFS2-3030 Computer Drive User Manual


 
FS-8700-130 Notifier NCA2/NFS-3030 Manual Page 13 of 22
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com
Appendix A. Advanced Topics
Appendix A.1. Notifier NCA2/NFS2-3030 Message Types Recognized
Event Keyword Clearing Event Notes
FIRE ALARM
CLEARED FIRE
ALARM
states: {1,0}
SECURITY
ALARM (LIFE)
CLEARED SECURITY
ALARM (LIFE)
states: {1,0}
LIFE CRITICAL
ALARM
CLEARED LIFE
CRITICAL ALARM
states: {1,0}
MEDICAL
EMERGENCY
CLEARED MEDICAL
EMERGENCY
states: {1,0}
SECURITY
ALARM
CLEARED SECURITY
ALARM
states: {1,0}
CRITICAL
PROCESS
CRITICAL PROCESS
states: {1,0}
SUPERVISORY
CLEARED
SUPERVISORY
states: {1,0}
TROUBLE/
FAULT
CLEARED
TROUBLE/ FAULT
States: [counter}
DISABLED
CLEARED
DISABLED
states: {1,0}
PREALARM
CLEARED
PREALARM
states: {1,0}
ACTIVE CLEARED ACTIVE states: {1,0}
ON/ OFF OFF states: {1,0}
SYSTEM
NORMAL
Resets all addresses in all memory areas but only if data is previously set
by driver and is not yet cleared by “Cleared” message and is configured
to Clear_on_Normal. By default Clear_on_Normal is “yes”.
SYSTEM RESET
Resets all addresses in all memory areas for a given Node but only if
data is previously set by driver and is not yet cleared by “Cleared”
message and is configured to Clear_on_Reset. By default
Clear_on_Reset is ‘no’.