FieldServer NCA2-NFS2-3030 Computer Drive User Manual


 
FS-8700-130 Notifier NCA2/NFS-3030 Manual Page 9 of 22
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com
4.3 Client Side Connection Descriptions
Section Title
Connections
Column
Title
Function Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8
2
Protocol Specify protocol used nfs2-nca; nca2; nfs2-3030
Baud* Specify baud rate
CRT Port
4800; 9600; 19200; 38400; 57600; (Vendor
limitation)
Printer Port
9600 (Vendor limitation)
Parity* Specify parity None (Vendor limitation)
Data_Bits* Specify data bits 8 (Vendor limitation)
Stop_Bits* Specify stop bits 1 (Vendor limitation)
Example
// Client Side Connections
Connections
Port ,Protocol ,Baud ,Stop_Bits ,Parity
P8 ,nfs2-nca ,9600 ,1 ,None
4.4 Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for Node Up to 32 alphanumeric characters
Node_ID
Station address of any physical Node on
network
1-240. Set unique Id for standalone Notifer-
3030 Panel
Protocol Specify protocol used nfs2-nca or nca2 ; nfs2-3030
Port
Specify which port the device is connected
to the FieldServer
P1-P8
Example
// Client Side Nodes
Nodes
Node_Name ,Node_ID ,Protocol ,Port
Panel_1 ,2 ,nfs2-nca ,P8
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.