4.2 Data Arrays/Descriptors
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Notifier NCA2/NFS2-3030 communications, the driver independent FieldServer buffers need to
be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side
Nodes” section, and the required data from Notifier Panels needs to be mapped in the “Client Side Map
Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
Section Title
Data_Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Up to 15 alphanumeric
characters
Data_Array_Format
Provide data format. Each Data Array can only take on one
format.
Bit, Sint16, Float1
Data_Array_Length
Number of Data Objects. Must be larger than the data
storage area required by the Map Descriptors for the data
being placed in this array.
1-10,000
Example 1
// Data Arrays
Data_Arrays
Data_Array_Name ,Data_Format ,Data_Array_Length
DA_SYS_N2 ,SINT16 ,508
DA_N2L01D ,BIT ,1749
DA_N2L01D_T ,SINT16 ,159
DA_N2L01M ,BIT ,1749
DA_N2L01M_T ,SINT16 ,159
DA_N2_PANEL ,BIT ,1056
DA_N2_PANEL_T ,SINT16 ,96
DA_N2_BELL_T ,SINT16 ,4
1
Sint16 is recommended over Float, as Float is memory expensive format