FieldServer NCA2-NFS2-3030 Computer Drive User Manual


 
FS-8700-130 Notifier NCA2/NFS-3030 Manual Page 18 of 22
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: (888) 509-1970 email: support@fieldserver.com
System Trouble Address System Trouble Address
LOOP CONTINUITY TEST FAIL LOOP 3
231
WALK TEST - FIRE PROTECTION IS LIMITED
485
LOOP CONTINUITY TEST FAIL LOOP 4 232 REMOTE PROG MODE ACCESSED 486
LOOP CONTINUITY TEST FAIL LOOP 5 233 DIA PROG. CHANGE DET. SERVICE REQUIRED 487
LOOP CONTINUITY TEST FAIL LOOP 6 234 ISIB DATA MESSAGE RECEIVED ERROR 488
LOOP CONTINUITY TEST FAIL LOOP 7
235
ISIB EXECUTIVE ROUTINE RE-ENTERED
489
LOOP CONTINUITY TEST FAIL LOOP 8 236 DIB TO SIB CABLE BAD OR MISSING 490
LOOP CONTINUITY TEST FAIL LOOP 9 237 UPLOAD/DOWNLOAD MESSAGE RECEIVED 491
LOOP CONTINUITY TEST FAIL LOOP 10 238 GLOBAL DATABASE MISMATCH 492
AMP FAIL 239 SIB PROG. CHANGE DET. SERVICE REQUIRED 493
AC FAIL 240 HS-NCM SNIFFER MODE ACTIVE 494
SCB ASSEM. COM. VERIFIED FAILED 241 EXCEEDED CONNECTION LIMIT 495
8255 PORT CHIP CONTROL WORD CHECK FAILE
242 NAM CCBE. PROG LOST 496
NETWORK COMMUNICATION LINK FAIL PORT A
243 MEMORY LOSS 497
NETWORK COMMUNICATION LINK FAIL PORT B
244 DVC COMM LOSS 498
STYLE 4 SHORT A L1 245 A.C. POWER LOSS. BACK UP ACTIVATED 499
STYLE 4 SHORT B L1 246 BUZZER OFF-LINE 500
STYLE 4 SHORT A L2 247 PANEL DOOR OPEN 501
STYLE 4 SHORT B L2
248
OFF NETWORK
502
STYLE 4 SHORT A L3 249 INSTALL. ERROR 503
STYLE 4 SHORT B L3 250 OR AUDIO/TELEPHON 504
STYLE 4 SHORT A L4 251 EXPANDER MODULES 505
STYLE 4 SHORT B L4
252
MANUAL CONTROL
506
STYLE 4 SHORT A L5 253 CAT. COMM. FAULT 507
STYLE 4 SHORT B L5 254 UNKNOWN 508
Appendix A.3. Node Status
Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of
data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the
NCA2 Panel is lost.
Node status offline/online (1/0) is stored in the 502
nd
address. It is important to read the Node status
before reading any information about the Node.
Node status data integrity itself depends upon system synchronization.
Appendix A.4. FieldServer Synchronization
There is currently no method of auto-synchronizing the FieldServer's Data Arrays with the Notifier NCA2/NFS2-
3030 panel because there is no method for polling the panel through the printer or CRT port. Synchronization of
the two devices can be achieved manually pressing the “System Reset” button on the panel while the FieldServer is
connected and running. All current events will be re-sent to the FieldServer..