Fujitsu M8000 Server User Manual


 
11-14 SPARC Enterprise M8000/M9000 Servers Service Manual October 2012
Caution – Do not forcibly push the cable in when inserting it. If the cable is forcibly
inserted despite the presence of any problems with the connector pin, serious damage may
result.
12. Switch on all main line switches for the AC section (ACS) in the power supply
system.
13. Confirm that the XSCF STANDBY LED (green) on the operator panel remains lit.
If it is blinking, wait until it remains lit.
14. Update the XSCF firmware.
In case the version of the firmware on the replaced XSCFU is different from the version
of the original, it is necessary to match the version of the firmware.
For the version matching of firmware, see the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide.
15. Set the XSCF clock.
From the terminal connected to XSCF, log in to XSCF and use setdate -s
MMDDhhmmCCYY.ss command to set the current time.
For details of the setdate command, see the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide, the SPARC Enterprise
M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference Manual, or the man page.
16. Use one of the following methods to start (power on) all domains at once.
Press and hold down (for less than four seconds) the POWER switch on the operator
panel.
From a console that is connected to XSCF, execute the poweron -a command of
XSCF.
The power to all the domains is turned on, and then the power-on self test (POST) is
executed. When ok prompt displayed on the console of relevant domain, POST is
completed.
For details of the power-on operation, see Section 4.4.2, “Powering the Server On” on
page 4-22, and the SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF
User’s Guide.
17. Confirm that the replacement components are normal by using the showhardconf
or showstatus command of XSCF.
Unless "*" is displayed for the replacement XSCFU, it is operating normally.
For details of the showhardconf command and showstatus command, see the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF User’s Guide, the
SPARC Enterprise M3000/M4000/M5000/M8000/M9000 Servers XSCF Reference
Manual, or the man page.