Drive Commissioning: Exit Reminder
After the Drive Commissioning wizard completes, the drive should have a hard
reset performed. This should clear any faults that have occurred because of
intermediate parameter values during the setup process.
The following wizards should be run to complete the start-up process:
Cell Test
Motor Control Tuneup
Speed Regulator Tuneup
Drive Commissioning: Conclusion
The Drive Commissioning Wizard has concluded.
Once this wizard is exited, the drive should have a hard reset performed. This
should clear any faults that have occurred because of intermediate parameter values
during the setup process.
The following wizards should be run to complete the start-up process:
Cell Test
Motor Control Tuneup
Speed Regulator Tuneup
Line Transfer Tuneup
Line Transfer Tuneup: Overview
The Line Transfer Tuneup wizard is provided to facilitate quick and reliable setup of
line transfer functions. This wizard allows the user to enable transfer functions and
direct I/O. If you are using the XferMtr command it will check phase rotation, and
measure the phase angle and voltage magnitude relationships needed to correctly
carryout the command. Because the wizard uses drive output instrumentation to do
these measurements it will generally be necessary for the user to manually close the
utility contactor to connect the drive output to the line. Depending on the application
it may be necessary to disconnect the motor in order to complete the wizard. Until
this wizard has be successfully completed the drive will not accept line transfer
commands.
There are many issues beyond drive software that must be considered before
attempting transfers and captures. For detailed information all applications issues see
the "Innovation Series Line Transfer Application Guide".
Line Transfer Tuneup: Motor Transfer Data
This wizard can configure the drive to perform motor transfer and capture
operations. The motor transfer data parameters configure the drive to transfer a
motor to the utility line. Enter the motor transfer data parameters.
Transfer mtr req sel selects the signal that initiates the motor transfer. Set as
required by your application.