GEH-6385 Reference and Troubleshooting, 2300 V Drives Chapter 3 Paramters/Functions
3-5
The following variable is also an input to the Capture Buffer function.
Variable Description
Capture buffer ready
Enables or disables the capture buffer data
collection.
Function Outputs
The following table specifies the status variables of the Capture Buffer function.
Variable Description
Capture buffer stat Indicates the status of the capture buffer. Possible
values are:
Complete - Capture buffer has completed its
collection of data and is disabled.
Wait for trigger - The capture buffer is waiting for the
evaluation of the trigger condition to go True.
Post trigger capt – Capture buffer has been triggered
and is collecting post trigger data.
Capture triggered Indicates if the capture buffer has been triggered.
True/False
Number of channels
Indicates the number of channels that the capture
buffer is configured to collect based on the setting of
Capture buff config.
Capture buffer depth
Indicates the depth (i.e. number of samples) of the
capture buffer. Capture buffer depth is inversely
proportional to the number of channels collected.
Capture samp period Indicates the interval at which the capture buffer
collects data based on the values of the parameters
Capture period and Capture period gain. Seconds
Total capture time
Indicates the total time that a full buffer would collect
based on the values of Capture buffer depth,
Capture period, and Capture period gain.