GE LP 33 Power Supply User Manual


 
Modifications reserved Page 28/57
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
Code Message Meaning
4602
Q1
OPEN
The auxiliary contact indicates that the output switch Q1 has
been opened.
4603
Q1
CLOSED
The auxiliary contact indicates that the output switch Q1 has
been closed.
4699
BATTERY TEST
IMPOSSIBLE
Not possible to start battery test (it is postponed) for:
No mains rectifier or bypass;
Battery not fully charged;
Load is below 10% or above 80%.
4763
REMOTE CONTROL
ON
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.
4764
REMOTE CONTROL
OFF
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.