OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
3. Telephone numbers set-up
Tel1:
Tel1 enabled: N
Tel2:
Tel2 enabled: N
Tel1: This parameter specifies a first tel. number to be used for
modem dial-out.
The telephone number has a maximum of 39 characters
and cannot contain intermediate blank.
If the desired number is shorter than 39 characters, finish
the string with blanks.
Tel1 enabled: this parameter Y/N specifies if the first telephone number will be used for dial-out.
Tel2: it records the second dial-out number.
Tel2 enabled: this parameter Y/N specifies if the second telephone number will be used for dial-out.
Tel3: it records the third dial-out number.
Tel3 enabled: this parameter Y/N specifies if the third telephone number will be used for dial-out.
Tel4: it records the fourth dial-out number.
Tel4 enabled: this parameter Y/N specifies if the fourth telephone number will be used for dial-out.
4. LCD Display
LCD Display
UPS NAME: LP 33
Language = ENGLISH
1. LCD display screen.
2. UPS name: the user can choice the name of the UPS model
showed on the main page (11 digits).
4. Language: his parameter allows the choice of language
used to display the information.
Valid choices are English, German, French,
Spanish, Italian, Finnish and Polish.
5. Operation mode selection (VFI Mode or ECO Mode)
NOTE !
The ECO Mode can only be activated on single units.
ECO Mode Y
d1 d2 d3 d4 d5 d6 d7
HOURS SELECTED
24 24 12 12 12 12 12
1. ECO Mode
This parameter (values Y / N) enables or disables the operation
in ECO Mode.
If the value is Y and the current time is in the interval for the current day, the ECO Mode is active.
The activation / disactivation of ECO Mode is indicated each time in the event list.
In order to check the inverter function, at least 1 minute of VFI Mode must be programmed during the
week (the Y / N parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI Mode is not respected, the ECO Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.