Modifications reserved Page 36/57
OPM_LPS_3UO_30K_40K_0US_V010.doc Operating Manual LP 33 Series 30 & 40 kVA
3. Switch On the output switch Q1 (Pos. I).
The output will be supplied by the mains through the bypass.
LP 33 40kVA
APPLICAT. ON UTILITY
= 70%
Verify, selecting the screen METERING/Udcp and Udcn, that the
booster voltage has reached about 215 VDC.
Udcp=215V Udcn=215V
Ubp=164V Ubn=164V F
Charge level = 100%
Autonomy = 800min
4. Switch On the inverter entering the screen:
MENU/COMMAND MENU/INVERTER ON
COMMAND MENU
INVERTER ON *
INVERTER OFF
Some seconds later the load will be transferred on inverter
and the main screen will display: APPLICATION ON UPS
LP 33 40kVA
APPLICATION ON UPS
= 70%
5. Operation mode selection.
LP 33 Series is delivered normally selected for permanent VFI operation.
ECO Mode can be enabled and the ECO START time & ECO STOP time can be programmed for each
day of the week (see Section 6.3.1-5).
END OF PROCEDURE
NOTE !
Even if the UPS is delivered with the battery fully charged, they could be partially
discharged during transportation or storage.
It is recommended to recharge the battery during a few hours in order to provide the
complete battery energy stored to the load in the event of mains failure.