Heatcraft Refrigeration Products H-IM-80C Network Card User Manual


 
15
SYSTEM DEFAULTS
Following are factory defaults for the parameters which can be programmed in
the Beacon II Smart Controller. If the user does not select a setting for any of
the following parameters, the default will be used.
It is important the user set ALL parameters based of their needs.
PARAMETERS CODE AIR ELECTRIC
Refrigerant
REFTYP
R22 R404A
Box Temperature
BOXTMP
35°F-10°F
Superheat
SUPRHT
8°F8°F
Smart Defrost
SMTDEF
N/A Off**
Defrost start times
DEF ST
9 AM/9 PM 4 AM, 10 AM, 4 PM, 10 PM
Defrost Fail-safe time
DEFSAF
40 min 30 min (60 min. when Smart Defrost is On)
Defrost End Temperature
DEFTMP
45°F60°F (55°F when Smart Defrost is On)
Alarm High Temperature
ALR HI
50°F5°F
Alarm Low Temperature
ALR LO
30°F-15°F
Alarm Time
ALRMIN
60 min 60 min
Temperature Units
°
F /
°
C
°F °F
Clock setting
12 / 24H
12 H 12 H
Test mode
TEST
Off Off
Service mode
SERVIC
Off Off
**When Smart Defrost is turned on, 8 defrost periods per day will automatically be
programmed. These will be at 12:00 am, 3:00 am, 6:00 am, 9:00 am, 12:00 pm, 3:00
pm, 6:00 pm, and 9:00 pm. Also, the defrost fail safe time will be set to 60 minutes,
and the defrost termination temperature will be set to 55°F. The user can change
these as needed for the application (for version 1.2).
System Defaults