HP (Hewlett-Packard) 651176-002 Tablet Accessory User Manual


 
Component identification 11
R/T3000 INT rear panel
Item Description
1
UPS option card
2
USB communications port
3
Serial communications port
4
Ground bonding screw
5
Load segment 1 and 2 (one IEC-320-C19 receptacle)
6
Load segment 1 (three IEC-320-C13 receptacles)
7
Load segment 2 (three IEC-320-C13 receptacles)
8
Cord retention clip attachment location
9
Cord retention clip attachment location
10
Cord retention clip attachment location
11
Ground bonding screw
12
REPO port
13
Input power receptacle (IEC-320-C19) for country-specific plug
attachment
REPO port
The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at the
UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port must be
connected to a remote, normally-open switch (not supplied). The REPO switch is used in conjunction with a
main disconnect device that removes the AC source from the input of the UPS. When the switch is closed:
The REPO feature immediately powers down protected devices and does not utilize the orderly
shutdown procedure initiated by power management software.
The REPO feature shuts down UPS units operating under either utility or battery power.
NOTE: If the UPS was operating on battery power when the remote switch was closed, no power
is available to the load devices until utility power is restored and the UPS has been manually
powered up.
To restore power to the load devices after the REPO feature is activated, press the On button after the AC
source is reconnected to the UPS.