HP (Hewlett-Packard) 651176-002 Tablet Accessory User Manual


 
Troubleshooting 55
Troubleshooting
LED troubleshooting
Utility
LED
On
Battery
LED
On
Bypass
LED
Self Test
LED
Battery
Fault LED
Site
Wiring
Fault LED
Over
Temp
LED
Overload
LED
Condition
OnLo
ad
<10%
Off Off OnLoa
d >10%
OnLoa
d >25%
OnLoa
d >50%
OnLoa
d >75%
Off UPS is in Operate mode (on
page 40)
Flashing
Off Off Off * * * Off UPS is in Standby mode (on
page 40)
Off
Off On OnLoa
d >10%
OnLoa
d >25%
OnLoa
d >50%
OnLoa
d >75%
Off UPS is in Auto-Bypass mode
(on page 41)
Flashing
Flashing Flashing Off Off Off Off Off UPS is in Converter Off mode
(on page 57)
Off
Off
Off
Off
Off
Off
Flashing
Flashing
General alarm condition (on
page 57)—UPS is in
Auto-Bypass mode
On
Off Flashing * * * * * Bypass is out of range (on page
58)
*
Off * Off Flashing * * * Battery condition (on page
58)—Batteries are
disconnected or battery test
failure
Off
Flashing Off Off Off Off Off Off Low battery (no utility power)
("UPS is on battery" on page
58)