HP (Hewlett-Packard) HP T1000 G3 Power Supply User Manual


 
ADDITIONAL UPS FEATURES
HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002
14
Table 1 DIP Switch Settings
100V Models
Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2
100V 90–106V ON ON
120V Models
Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2
110V 99–116V ON OFF
120V* 108–127V* OFF OFF or ON
230V Models
Output Voltage Input Voltage Range DIP Switch 1 DIP Switch 2
220V 198–233V ON OFF
230V* 207–243V* OFF OFF or ON
240V 216–254V ON ON
* Default position
 Communication Options
The UPS is equipped with a USB port and a serial port. Either the USB port or the serial
port may be used to monitor the UPS; however, they cannot operate simultaneously.
 USB Port
The UPS can communicate with a USB-compliant computer using HP Power Manager
software.
To establish communication between the UPS and a computer:
1 Connect the USB cable to the USB port on the UPS rear panel.
Connect the other end of the USB cable to the USB port on your computer.
USB Port
Figure 15 The USB Port
2 Install the HP Power Manager software according to the instructions provided with
the software.