HP (Hewlett-Packard) HP T1000 G3 Power Supply User Manual


 
SPECIFICATIONS
HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002
25
Table 6 Electrical Output
100V Models 120V Models 230V Models
Power Levels (rated at nominal
inputs)
100V: 750 VA, 500W
1000 VA, 680W
1200 VA, 980W
110V and 120V: 750 VA, 500W
1000 VA, 670W
120V: 1400 VA, 950W
750 VA, 500W
1000 VA, 670W
1400 VA, 950W
Power Factor 0.67
Regulation (Normal mode) -10% to +6% of nominal voltage
Regulation (Battery mode),
Nominal Voltage ±5%
Same as selected nominal input
voltage
100V
Same as selected nominal input
voltage
110V, 120V
Same as selected nominal
input voltage
220V, 230V, 240V
Voltage Waveform Sine wave
Overcurrent Protection Inverter saturation current limited
Output Receptacles HP T750J, HP T1000J, and
HP T1500J: (6) 5-15
HP T750 G2: (4) 5-15
HP T1000 G3 and HP T1500 G3:
(6) 5-15
HP T750 G2:
(4) 10A, IEC-320
HP T1000 G3 and HP
T1500 G3: (6) 10A, IEC-320
Table 7 Environmental and Safety
100/120V Models 230V Models
Operating Temperature Up to 1,500 meters: 0°C to 40°C (32°F to 104°F); UL tested 25°C (77°F)
Above 1,500 meters: 0°C to 35°C (32°F to 95°F)
Transit/Storage Temperature -15°C to 55°C (5°F to 131°F)
Relative Humidity 5–95% noncondensing
Operating Altitude Up to 3,000 meters above sea level
Audible Noise Less than 45 dBA typical
Surge Suppression ANSI C62.41 Category A (formerly IEEE 587)
Safety Conformance UL 1778 2nd Edition; UL 497A;
CSA C22.2, No. 107.1
IEC/EN 62040-1-1 and IEC/EN 60950-1
Safety Markings cULus, cUL, NOM-NYCE CE, TÜV, C-Tick, GOST R, EK, IRAM, TISI
EMC (Class B) FCC Part 15, ICES-003, VCCI IEC/EN 62040-2, FCC Part 15, ICES-003, VCCI