HP (Hewlett-Packard) MMS and MRS Switch User Manual


 
290 CSI Section 16160
Siemens Electrical Products and Systems
Specification Guide
AC Controls
15
General / Wiring Diagrams
AC Controls
Manual Motor Starters and Contactors
Application
Across the line manual motor starters
and contactors provide control for
machinery where start stop remote con-
trol is not required (optional remote stop
available). Class 11 manual starters are
used for single and polyphase motors up
to 10 Hp. Starters have melting alloy
overload relays which help protect
against damage due to excessive current
caused by a sustained overload, low line
voltage, or single phasing of the motor.
Contactors provide control for inherently
protected motors. Typical applications
include metal and wood-working machin-
ery, grinders, power saws, conveyors,
fans pumps, blowers, textile and packag-
ing machinery, slitters, and paper cutters.
Features
Class 11 manual controllers have front
accessible pressure type wire connec-
tors. Ample wiring space is provided for
easy wiring.
A complete line of general purpose and
industrial duty enclosures is available as
well as open type mounting for custom
built enclosures. These manual con-
trollers are available with low voltage pro-
tection which will automatically open the
power poles when the voltage drops or
the power is interrupted. A remote stop
function may be incorporated with the
low voltage protection coil as a factory
option to provide remote or semi-auto-
matic operation.
Class 11 controllers provide the OSHA
requirements for protecting personnel
from potential injury caused by the auto-
matic start up of machinery following a
voltage drop or power interruption when
low voltage protection is specified.
Open styles and devices in NEMA 1, 4, 7
& 9, 12 enclosures can be padlocked in
the OFF position.
Type
1-Phase
3-Phase
M0
Size 115 Volts 200/230 Volts
Type Size 200/230 Volts 460/575 Volts
12
M1
23
M0
35
M1
710
M1P
35
Table 15.11
Class 11 Manual Motor Starters
Maximum Horsepower
1
2