HP (Hewlett-Packard) R7000 Power Supply User Manual


 
Specifications 51
UPS model Load
segment
Circuit
breaker
Output receptacles Maximum current
1 x L6-30R
Up to full UPS power rating
2 20 A¹ 2 x IEC-320-C19 16 A per receptacle²
2 x IEC-320-C13 10 A per receptacle
R7000 INTL
1 20 A¹ 2 x IEC-320-C19 16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
1 x IEC-309-32A Up to full UPS power rating
2 20 A¹ 2 x IEC-320-C19 16 A per receptacle²
2 x IEC-320-C13 10 A per receptacle
1
The circuit breakers protect the C19 and C13 outlets.
2
If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension
bar is 10 A. The total maximum current for the extension bar is 12 A.
Power protection specifications
UPS model VA Nominal power
rating (W)
Nominal voltage
setting
R7000 NA/JPN
7200 7200 200/208, 220,
230, 240
R7000 INTL
6500 6500 220, 230, 240
Voltage specifications
Configuration setting (VAC) Available nominal output voltage
(VAC)
200/208
204
220
220
230
230
240
240
Output tolerance specifications
Source of power Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
Battery power
±5% of nominal output voltage rating
Output feature specifications
Feature Specification
Online efficiency
94% nominal input voltage