HP (Hewlett-Packard) R7000 Power Supply User Manual


 
Overview 6
Overview
UPS R7000 overview
The HP UPS R7000 features a 4U rackmount design and offers power protection for loads up to 7200
VA/7200 W (NA/JPN) or 6500 VA/6500 W (INTL).
UPS R7000 features
Features include:
4U UPS height, 3U ERM height
ERM technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life
Extended runtime with up to four ERMs per UPS
Easily replaceable battery modules that simplify maintenance
Emergency shutdown control through the REPO port
HP UPS Network Module network connectivity with monitoring and control
Firmware that is service upgradeable through the standard DB-9 communication port
Backed by worldwide agency approvals
To benefit from the latest product enhancements, update to the latest versions of UPS firmware and software.
NOTE: To download the latest versions of UPS firmware and software, see the HP website
(http://www.hp.com/go/rackandpower).
Important safety information
WARNING: To reduce the risk of fire, only connect unit input to a circuit provided with branch
circuit overcurrent protection for 40 A rating in accordance with the National Electric Code,
ANSI/NFPA 70.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source
from the ground.
WARNING: Contact with any part of a grounded battery can result in electrical shock. Shock risk
is reduced if grounds are removed during installation and maintenance.