HP (Hewlett-Packard) UPS R1500 GENERATION 2 Power Supply User Manual


 
Installation 19
Selecting the UPS voltage configuration
Using a small tool, position the DIP switches according to the desired voltage configuration.
NOTE: An asterisk (*) indicates the default setting.
Output voltage Input voltage range DIP switch 1 DIP switch 2
R1500 G2
JPN/TWN
100 V* 90106 V Down Down
110 V 99116 V Down Up
R1500 G2 NA 110 V 99116 V Down Up
120 V* 108127 V Up N/A
R1500 G2 INTL 220 V 198233 V Down Up
230 V* 207243 V Up N/A
240 V 216254 V Down Down
Connecting the host computer
CAUTION: Only one communications port can be connected to the host computer.
Connecting more than one will result in unexpected UPS behavior. If an option card is
installed, the serial and USB communications ports are automatically disabled.
Connect the UPS to a host computer using either the USB cable or the DB9 serial cable included with the
UPS. Install HP Power Manager software 4.0 or later on the host computer. See the HP website
(http://www.hp.com/go/rackandpower
) to download the latest version of HP Power Manager.
NOTE: To install and configure the software, see the software user guide. The software user
guide is available for download from the HP website
(http://www.hp.com/go/rackandpower
).